The TUNZE forum is a direct link between TUNZE Aquarientechnik GmbH and the aquarists. You are welcome to ask any question on technical backgrounds, water treatment and water biology in combination with TUNZE components. If you have any questions in case of technical problems, please access our “Technical assistance” section; please refer to the table of contents. If you want to ask a question in this forum, you automatically agree to the fact that we may mention your last name and country of residence when presenting your question in this forum.

Electrical safety

Electrical safety



Enquiry from Mr. Maier / Germany

Could any of you say, whether DI circuit-breakers make sense in the household (I have also heard about FI circuit-breakers (earth-leakage circuit-breakers) ?
Or is handling in the aquarium still too risky even when using such a circuit-breaker .


Answer

à DI and FI circuit-breakers have the same function. They consist of a safety switch, which disconnect the current if an offset current occurs on any pole.
à Safety always makes sense and particularly where current in damp rooms is concerned. Of course, all the electrical parts of an aquarium pump are encased in resin, for example, but there is still the danger that a heating unit breaks or a lamp falls into the water, etcetera.
à In respect of units, which feature all the electrical safety marks and are additionally connected to an FI circuit-breaker, there should actually be no hazard any more. Nevertheless, we recommend to switch off electrical equipment before handling in an aquarium.